A class is a test result. The door is built as it will be delivered — same fabric, same guides, same fixings — and loaded with air pressure across the leaf until the class pressure is reached. It has to stay in its guides, stay operable and deflect no more than the standard permits. The class is the pressure it held, not the wind it will meet.
Two consequences follow, and both matter more than the number itself. A class belongs to a tested assembly, so changing the fabric, the guide section or the fixing centres invalidates it. And a class says nothing about the building: the structure that receives the guide-column reactions is checked separately, by whoever is responsible for the frame.
The common misreading
„Class 4 is enough — we are not on the coast.”
An open airfield 60 km inland can demand the same class as a quayside hall, because terrain roughness and the height of the leaf drive the gust pressure as hard as distance from the sea does. Sheltered means screened upwind of this opening — not somewhere in the region.